Page 53 - Dell PowerEdge R620 Technical Guide
P. 53
Table 32 lists power supply specifications for the PowerEdge R620.
Specification 1100W DC 1100W AC 750W AC 495W AC
Current consumption 32A 12A–6.5A 10A–5A 6.5A–3A
1
1
1
Supply voltage -48V to -60V DC 100–240VAC 100–240VAC 100–240VAC
Frequency N/A 50/60Hz 50/60Hz 50/60Hz
2
2843
Heat dissipation (BTU/hr max) 4416 4100 3 1908
2891
1 Auto-ranging
2
Titanium efficiency
3
Platinum efficiency
Table 33 details the environmental specifications for the R620. For additional information about
environmental measurements for specific system configurations, see
Dell.com/environmental_datasheets.
Fresh Air: temperature, humidity, altitude de-rating
Continuous 10°C to 35°C (50°F to 95°F) at 10% to 80% relative humidity with 26°C (78.8°F) maximum
operation dew point (maximum wet bulb temperature). De-rate maximum allowable dry bulb
temperature at 1°C per 300m above 950m (1°F per 547 ft above 3117 ft).
Expanded When operating in the expanded temperature range, system performance may be impacted,
operation and ambient temperature warnings may be reported on the LCD and in the System Event
Log.
≤ 10% of annual operating hours: 5°C to 10°C and 35°C to 40°C (with no direct sunlight on
the equipment) at 5% to 85% relative humidity with 26°C dew point (maximum wet bulb
temperature). Outside the standard operating temperature (10°C to 35°C), the system can
operate down to 5°C or up to 40°C for a maximum of 10% of its annual operating hours. For
temperatures between 35°C and 40°C (95°F to 104°F), de-rate maximum allowable dry bulb
temperature by 1°C per 175m above 950m (1°F per 319 ft above 3117 ft).
≤ 1% of annual operating hours: –5°C to 5°C and 40°C to 45°C (with no direct sunlight on
the equipment) at 5% to 90% relative humidity with 26°C dew point (maximum wet bulb
temperature). Outside the standard operating temperature (10°C to 35°C), the system can
operate down to –5°C or up to 45°C for a maximum of 1% of its annual operating hours. For
temperatures between 40°C and 45°C (104°F to 113°F), de-rate maximum allowable dry bulb
temperature by 1°C per 125m above 950m (1°F per 228 ft above 3117 ft).
Expanded operation restrictions:
No cold startup below 5°C
Maximum altitude for the operating temperature must be 3050m (10,000ft)
Redundant power supplies required
Not supported:
- Express Flash PCIe SSD
- GPU